SCOP Explained: How to Evaluate Heat Pump Efficiency Icon

SCOP Explained: How to Evaluate Heat Pump Efficiency

Why the SCOP Matters

EU energy label of a heat pump with SCOP indication

Anyone looking to buy a heat pump will inevitably encounter efficiency metrics like COP, SCOP, and SPF. The SCOP has established itself as the central figure: it appears on the EU energy label, determines subsidy eligibility, and enables realistic comparison between different units.

Unlike the COP, which represents only a momentary value under laboratory conditions, the SCOP reflects efficiency over a complete heating season. This accounts for varying outdoor temperatures throughout the year – from mild autumn days to cold winter nights.

This article explains how the SCOP is calculated, what values are considered good, and what to look for when comparing heat pumps.

What is the SCOP?

SCOP stands for Seasonal Coefficient of Performance – a seasonally-adjusted performance coefficient. The value indicates how much heat energy a heat pump generates on average during a heating season from one kilowatt-hour of electricity.

The calculation follows the European standard EN 14825. Unlike the COP, which is measured at a single temperature, the SCOP incorporates multiple operating points.

The Four Measurement Points

For the middle climate zone (which includes Germany and most of Central Europe), COP values are determined at the following outdoor temperatures:

Measurement Point Outdoor Temperature Share of Heating Season
Point 1 +12 °C Transition period (frequent)
Point 2 +7 °C Mild winter
Point 3 +2 °C Normal winter
Point 4 –7 °C Cold winter (rare)

These individual values are then combined with weighting. Since mild temperatures occur more frequently in Central Europe than severe frost, the measurement points at +7 °C and +2 °C have the greatest influence on the SCOP.

Mind the Flow Temperature

The SCOP is specified for different flow temperatures. Common designations are:

  • SCOP 35 (also LT for Low Temperature): For low-temperature systems like underfloor heating
  • SCOP 55 (also MT for Medium Temperature): For conventional radiators

The SCOP 35 is always higher than the SCOP 55 because the heat pump operates more efficiently at lower flow temperatures. The EU energy label standardly shows the SCOP for 55 °C – this is the more relevant value for consumers, as many existing buildings require higher flow temperatures.

The Three European Climate Zones

The EU divides Europe into three climate zones with different temperature profiles for SCOP calculation:

Climate Zone Reference Location Typical Countries Additional Measurement Point
Northern Europe Helsinki Finland, Sweden, Norway –15 °C
Central Europe Strasbourg Germany, Austria, Switzerland, France
Southern Europe Athens Greece, Spain, Italy +2 °C omitted

The EU energy label always shows the SCOP for the middle climate zone (Strasbourg profile). Manufacturers may additionally specify values for other zones.

For buyers in Central Europe, the Strasbourg profile is appropriate. Those living in alpine regions or northern areas should consider that actual efficiency may be somewhat lower than the stated SCOP.

SCOP vs. COP vs. SPF – The Difference

Overview of COP, SCOP and SPF metrics

These three metrics are often confused, although they make different statements:

COP (Coefficient of Performance)

The COP is a momentary value under standardised laboratory conditions. It is measured according to EN 14511 at fixed temperatures, for example:

  • A2/W35: Air 2 °C, flow temperature 35 °C
  • B0/W35: Brine (ground) 0 °C, flow temperature 35 °C

The COP is suitable for direct technical comparison of units under identical conditions. However, it says little about efficiency in real operation.

SCOP (Seasonal COP)

The SCOP is a weighted average of multiple COP values over a typical heating season. It is more realistic than the COP because it considers various outdoor temperatures. The SCOP forms the basis for the EU energy label and subsidy requirements.

SPF (Seasonal Performance Factor)

The SPF is the actual efficiency value of an installed heat pump over an entire operating year. It can only be measured after installation and considers all individual factors: building insulation, user behaviour, regional climate, system settings.

When Each Value is Relevant

Situation Relevant Metric
Comparing units before purchase SCOP (and COP for technical comparison)
Applying for subsidies ηs (based on SCOP)
Checking efficiency of own system SPF
Creating energy certificate SPF according to VDI 4650

What is a Good SCOP Value?

Achievable SCOP values depend heavily on the heat pump type and flow temperature. Generally: the more constant the heat source, the higher the SCOP.

Reference Values by Heat Pump Type

At 35 °C flow temperature (underfloor heating):

Heat Pump Type Average Good Very Good
Air-to-water 3.5–4.0 4.0–4.5 > 4.5
Ground source 4.2–4.7 4.7–5.2 > 5.2
Water-to-water 5.0–5.5 5.5–6.5 > 6.5

At 55 °C flow temperature (radiators):

Heat Pump Type Average Good Very Good
Air-to-water 2.8–3.2 3.2–3.6 > 3.6
Ground source 3.3–3.8 3.8–4.2 > 4.2
Water-to-water 4.0–4.5 4.5–5.0 > 5.0

Why Ground Source Heat Pumps Perform Better

Air-to-water heat pumps have a systematic disadvantage: when it's coldest outside and heating demand is highest, efficiency drops. At –7 °C outdoor temperature, an air-to-water heat pump operates significantly less efficiently than at +7 °C.

Ground source and water-to-water heat pumps, however, use heat sources with nearly constant temperatures: the ground at 1.5 m depth maintains approximately 8–12 °C year-round, and groundwater consistently stays at 8–12 °C. These stable conditions enable higher SCOP values.

Inverter Technology Improves SCOP

Modern heat pumps with inverter technology can continuously adjust their output to demand. In partial load operation – that is, in mild weather when little heating output is needed – they work particularly efficiently.

Inverter modulation can achieve SCOP improvements of 8–15% compared to fixed-speed heat pumps. Top devices today achieve SCOP values above 5.0 at 35 °C flow temperature.

ηs: The Seasonal Space Heating Energy Efficiency

For subsidies in Germany (BAFA and KfW), the decisive factor is not the SCOP directly but the derived ηs value (Greek: eta-s). ηs represents the seasonal space heating energy efficiency and is expressed as a percentage.

The Formula

ηs (%) = (SCOP ÷ 2.5) × 100

The divisor 2.5 is the primary energy factor for the European electricity mix. It accounts for the fact that generating 1 kWh of electricity requires approximately 2.5 kWh of primary energy at the power plant.

Calculation Examples

SCOP ηs Calculation ηs
3.0 3.0 ÷ 2.5 × 100 120%
3.5 3.5 ÷ 2.5 × 100 140%
4.0 4.0 ÷ 2.5 × 100 160%
4.5 4.5 ÷ 2.5 × 100 180%
5.0 5.0 ÷ 2.5 × 100 200%

An ηs above 100% means: more heating energy is generated from the primary energy input than would be possible through direct combustion.

Subsidy Requirements

For the German Federal Subsidy for Efficient Buildings (BEG), minimum requirements apply for the ηs value:

Heat Pump Type ηs 35 min. ηs 55 min.
Air-to-water (electric) 135% 120%
Ground source (electric) 150% 135%
Water-to-water (electric) 150% 135%

An ηs 35 of 135% corresponds to a SCOP of 3.375. Most current air-to-water heat pumps easily meet this requirement.

SCOP on the EU Energy Label

Since 2019, all heat pumps must carry an EU energy label. The efficiency scale ranges from A+++ (best class) to D (lowest still permitted class).

What the Label Shows

The energy label for heat pumps contains:

  • The energy efficiency class (A+++ to D)
  • The heating output in kW
  • The sound power level in dB(A)
  • The SCOP for the middle climate zone at 55 °C flow temperature

Efficiency Classes and SCOP

Efficiency Class SCOP (at 55 °C) Typical Heat Pumps
A+++ ≥ 5.1 Best ground source and water heat pumps
A++ 4.6–5.1 Good ground source, best air-to-water
A+ 4.0–4.6 Standard air-to-water heat pumps
A 3.4–4.0 Basic models

Most air-to-water heat pumps achieve A++ at 35 °C flow temperature but only A+ at 55 °C. Ground source and water heat pumps achieve A++ or A+++ even at higher flow temperatures.

Practical Example: SCOP Comparison with Cost Calculation

A concrete example shows how different SCOP values affect operating costs.

Initial Situation

  • Single-family home with 150 m²
  • Heat demand: 15,000 kWh per year
  • Electricity price: €0.30/kWh

Comparison of Two Heat Pumps

Feature Heat Pump A Heat Pump B
Type Air-to-water Air-to-water
SCOP (55 °C) 3.2 3.8
Purchase price €12,000 €15,000

Electricity Consumption and Costs

Heat Pump A (SCOP 3.2):

  • Electricity consumption: 15,000 kWh ÷ 3.2 = 4,688 kWh/year
  • Electricity costs: 4,688 × €0.30 = €1,406/year

Heat Pump B (SCOP 3.8):

  • Electricity consumption: 15,000 kWh ÷ 3.8 = 3,947 kWh/year
  • Electricity costs: 3,947 × €0.30 = €1,184/year

Savings and Payback

The more efficient Heat Pump B saves €222 annually in electricity costs. The additional cost of €3,000 is thus recovered in approximately 13.5 years – faster with rising electricity prices.

Tip: With our Heat Pump Calculator you can calculate the seasonal performance factor and operating costs for your individual situation according to VDI 4650.

Conclusion

The Bottom Line: The SCOP is the most meaningful metric for comparing heat pump efficiency before purchase. It accounts for the seasonal temperature fluctuations of a heating period and forms the basis for the EU energy label as well as subsidy requirements. When evaluating, always note the specified flow temperature: the SCOP 35 for low-temperature systems is always higher than the SCOP 55 for conventional radiators. Ground source and water heat pumps fundamentally achieve higher SCOP values than air-to-water heat pumps due to their constant heat source.

In daily operation, the actual efficiency value – the seasonal performance factor (SPF) – will deviate from the SCOP because individual factors such as building insulation, heating behaviour, and regional climate come into play. Nevertheless, the SCOP remains the best available comparison value for the purchasing decision.


Heat Pump Article Series

No. Article Topic
0 Heat Pump: The Complete Guide Overview and introduction
1 The Anti-Refrigerator: How Does a Heat Pump Work? Physical fundamentals
2 The Components: Heat Exchanger, Compressor and Expansion Valve Components in detail
3 Key Figures and Sizing of Heat Pumps COP, SPF, sizing
4 Operating Modes: Monovalent, Bivalent and Hybrid Operating modes explained
5 Heat Pump Types and the Dream Team with Solar Systems Types & combination with PV
6 SCOP Explained: Evaluating Heat Pump Efficiency You are here

Further Reading

The article Key Figures and Sizing explains further important metrics like GWP (global warming potential of the refrigerant) and provides rules of thumb for proper sizing. Those interested in combining heat pumps with photovoltaics will find practical recommendations in the article Heat Pump Types and the Dream Team with Solar Systems.

Sources


Calculate Your SPF Now

With our free Heat Pump Calculator, calculate the seasonal performance factor of your heat pump according to VDI 4650 – including operating costs and CO₂ balance.

→ To the Heat Pump Calculator