pv-calor.com
Transmission Heat Losses Icon

Transmission Heat Losses: When Heat Passes Through Walls

Transmission heat losses occur when heat "flows" through solid building components from inside to outside. In most buildings, they account for 60–80% of the total heating load and are therefore the most important starting point for energy renovations.

The Physical Principle

Heat always flows from warm to cold – this is the second law of thermodynamics. In a heated building, this means:

  • Inside: 20°C (warm)
  • Outside: -10°C (cold)
  • Temperature difference: 30 K (Kelvin)

The greater the temperature difference, the more heat flows outward.

Analogy: Imagine a hot cup of coffee. The colder the surroundings, the faster it cools down. The cup is like the building envelope – the better insulated (thermos flask), the slower the heat loss.

The Three Modes of Heat Transfer

Heat can be transferred in three ways:

Mode Description Example in Buildings
Conduction Through solid materials Through the wall
Convection Through moving air Air movement at surfaces
Radiation Through electromagnetic waves Heat radiation from the wall

In transmission, all three work together:

  1. Heat is transferred from room air to the inner wall (convection + radiation)
  2. Heat conducts through the wall (conduction)
  3. Heat is released from the outer wall to outside air (convection + radiation)

The Calculation Formula

Transmission heat losses are calculated according to DIN EN 12831-1:

Formula: ΦT = HT × (θi - θe)

with HT = Σ (U × A × fT) + ΔUWB × A

  • ΦT = Transmission heat loss (W)
  • HT = Transmission heat loss coefficient (W/K)
  • θi = Indoor temperature (°C)
  • θe = Design outdoor temperature (°C)
  • U = U-value of the component (W/m²K)
  • A = Area of the component (m²)
  • fT = Temperature correction factor
  • ΔUWB = Thermal bridge surcharge (W/m²K)

The Temperature Correction Factor fT

Not all components border directly on outside air. The factor fT accounts for this:

Adjacent to fT Explanation
Outside air 1.0 Full temperature difference
Unheated basement 0.5 Basement is warmer than outside
Ground 0.3–0.6 Ground temperature relatively constant
Unheated garage 0.8 Garage somewhat warmer than outside
Heated neighbour 0.0 No temperature difference

Example: A basement ceiling with U = 0.5 W/m²K and fT = 0.5 has the same effective heat loss as an external wall with U = 0.25 W/m²K.

Building Components and Their U-Values

The most important components and typical U-values compared:

External Walls

Construction Period Wall Type U-Value Rating
before 1970 Solid brick 36cm 1.4–1.6 W/m²K Poor
1970–1990 Hollow block 30cm 0.8–1.2 W/m²K Moderate
1990–2010 Aerated concrete 30cm 0.4–0.6 W/m²K Medium
after 2010 ETICS 16cm 0.2–0.3 W/m²K Good
Passive house ETICS 30cm+ < 0.15 W/m²K Very good

Windows

Generation Glazing U-Value (Uw) Rating
before 1980 Single glazing 5.0–5.8 W/m²K Very poor
1980–1995 Double without Low-E 2.7–3.0 W/m²K Poor
1995–2010 Double with Low-E 1.3–1.6 W/m²K Medium
after 2010 Triple with Low-E 0.7–1.0 W/m²K Good
Passive house Triple special < 0.8 W/m²K Very good

Roof

Insulation U-Value Rating
Uninsulated 2.0–3.0 W/m²K Very poor
8cm insulation 0.4–0.5 W/m²K Moderate
16cm insulation 0.2–0.25 W/m²K Good
24cm+ insulation < 0.15 W/m²K Very good

Calculation Example

A room with the following components at θi = 20°C and θe = -12°C:

Component Area U-Value fT HT Contribution
External wall 15 m² 0.28 W/m²K 1.0 4.2 W/K
Window 4 m² 1.3 W/m²K 1.0 5.2 W/K
Roof 12 m² 0.20 W/m²K 1.0 2.4 W/K
Basement ceiling 20 m² 0.35 W/m²K 0.5 3.5 W/K
Total 15.3 W/K

Calculation: ΦT = 15.3 W/K × (20°C - (-12°C)) = 15.3 × 32 = 489.6 W

The room loses almost 490 watts through transmission at -12°C outdoor temperature.

Where Do the Greatest Heat Losses Occur?

Typical distribution of transmission heat losses:

Component Share Why?
Windows 25–35% High U-values despite small area
External walls 25–30% Large area
Roof 15–25% Warm air rises
Basement/floor 10–15% Partially buffered by ground
Thermal bridges 5–15% Often underestimated

Note: Windows may have the smallest area but often the highest U-value. A 2 m² window with U = 1.3 W/m²K loses as much heat as 10 m² of well-insulated wall with U = 0.26 W/m²K!

Measures for Reduction

1. External Wall Insulation

Measure Investment U-Value Improvement
ETICS 12cm £70–100/m² from 1.4 to 0.28 W/m²K
Cavity insulation £15–35/m² from 1.0 to 0.4 W/m²K
Internal insulation £40–70/m² from 1.4 to 0.5 W/m²K

2. Window Replacement

Measure Investment U-Value Improvement
Double → Triple £250–400/m² from 1.4 to 0.9 W/m²K
Complete new (triple) £350–500/m² depending on starting condition

3. Roof Insulation

Measure Investment U-Value Improvement
Between rafters 16cm £35–50/m² from 0.5 to 0.22 W/m²K
Above rafters 20cm £85–130/m² from 0.5 to 0.16 W/m²K
Top floor ceiling £15–35/m² from 0.8 to 0.18 W/m²K

The Heating Load Calculator

Our Heating Load Calculator calculates transmission heat losses automatically:

  • Component catalogue with over 150 typical constructions
  • Automatic U-value determination by construction period
  • Correction factors for ground contact, unheated spaces etc.
  • Thermal bridge surcharges by construction standard

Calculate now: Determine the transmission heat losses of your building with our Heating Load Calculator.


Further Reading


Sources

  • DIN EN 12831-1:2017-09 – Method for calculation of the design heat load
  • DIN 4108-2 – Thermal protection in buildings
  • DIN EN ISO 6946 – Building components – Thermal resistance and U-value