Ventilation Heat Losses: When Warm Air Escapes
Ventilation heat losses occur when warm indoor air leaves the building and is replaced by cold outdoor air. They typically account for 20–40% of the heating load – in very well-insulated buildings even more.
The Principle
Air is a heat carrier. When 20°C warm indoor air is replaced by -10°C cold outdoor air, the heating system must compensate for this temperature difference:
- Warm air out = Heat energy is lost
- Cold air in = Must be heated up
- Result: Additional heating demand
Analogy: Imagine a bathtub filled with warm water. If you constantly drain warm water and refill with cold, you must continuously reheat to maintain the temperature.
The Calculation Formula
Ventilation heat losses are calculated according to DIN EN 12831-1:
Formula: ΦV = HV × (θi - θe)
with HV = V × n × ρ × cp = V × n × 0.34
- ΦV = Ventilation heat loss (W)
- HV = Ventilation heat loss coefficient (W/K)
- V = Room volume (m³)
- n = Air change rate (1/h)
- ρ × cp = 0.34 Wh/(m³K) for air
- θi = Indoor temperature (°C)
- θe = Design outdoor temperature (°C)
Air Change Rate: The Decisive Factor
The air change rate n indicates how often the room volume is exchanged per hour:
| n | Meaning | Example |
|---|---|---|
| 0.5 1/h | Half the volume per hour | Well-sealed building |
| 1.0 1/h | Entire volume per hour | Average |
| 2.0 1/h | Double volume per hour | Draughty old building |
Minimum Air Change According to DIN EN 12831-1
The standard defines a hygienically necessary minimum air change:
| Room type | Minimum n | Reason |
|---|---|---|
| Living rooms | 0.5 1/h | CO2 removal, moisture |
| Bedrooms | 0.5 1/h | Moisture from occupants |
| Kitchen | 1.0–1.5 1/h | Cooking fumes, humidity |
| Bathroom | 1.5–2.0 1/h | High humidity |
| WC | 1.5 1/h | Odours |
Important: Insufficient ventilation leads to moisture damage and mould! The minimum air change is non-negotiable – it must be covered by the heating load.
The Two Types of Air Exchange
1. Infiltration (Uncontrolled)
Air exchange through leakage in the building envelope:
- Joints around windows and doors
- Penetrations (pipes, cables)
- Leaks at connections
- Porous building materials
Infiltration depends heavily on building airtightness, measured as the n50 value (air change at 50 Pa pressure difference):
| Building type | n50 value | Infiltration in windy conditions |
|---|---|---|
| Unrefurbished old building | 6–10 1/h | 0.5–1.0 1/h |
| Refurbished with new windows | 3–5 1/h | 0.2–0.4 1/h |
| New build to Building Regs | 1.5–3.0 1/h | 0.1–0.2 1/h |
| Passivhaus | < 0.6 1/h | < 0.05 1/h |
2. Mechanical Ventilation (Controlled)
Targeted air exchange through ventilation systems:
| System | Description | Heat recovery |
|---|---|---|
| Extract-only system | Only extract air is mechanical | None |
| Balanced system (MVHR) | Both supply and extract mechanical | Possible (HRV) |
| Decentralised units | Single-room solutions | Often integrated |
Heat Recovery (HRV)
Modern ventilation systems can recover 60–95% of the heat from extract air:
Formula with HRV: ΦV = V × n × 0.34 × (1 - ηHRV) × (θi - θe)
- ηHRV = Heat recovery efficiency (e.g. 0.85 = 85%)
| HRV efficiency | Effective temperature difference | Heating load reduction |
|---|---|---|
| 0% (without HRV) | 32 K (at -12°C outside) | Reference |
| 75% | 8 K | -75% |
| 85% | 4.8 K | -85% |
| 95% | 1.6 K | -95% |
Example: A room with 50 m³ and n = 0.5 1/h has a ventilation heat loss of 272 W without HRV. With 85% HRV, this drops to just 41 W – a saving of 231 W!
Worked Example
A living room with:
- Volume: V = 60 m³
- Air change: n = 0.5 1/h
- Indoor temperature: θi = 20°C
- Outdoor temperature: θe = -12°C
Without Heat Recovery
Calculation: HV = 60 m³ × 0.5 1/h × 0.34 = 10.2 W/K
ΦV = 10.2 W/K × (20 - (-12)) K = 10.2 × 32 = 326 W
With 85% Heat Recovery
Calculation: ΦV = 326 W × (1 - 0.85) = 326 × 0.15 = 49 W
Saving: 277 W = 85%
Ventilation Concepts Compared
| Concept | Advantages | Disadvantages | Effect on heating load |
|---|---|---|---|
| Window ventilation | No investment, flexible | Heat loss, user-dependent | High (full ventilation losses) |
| Extract-only system | Inexpensive, moisture protection | No HRV | Medium |
| MVHR with HRV | Energy-efficient, comfortable | High investment | Low (up to -90%) |
| Decentralised units | Retrofittable, HRV possible | Noise, appearance | Low to medium |
Effect on Building Heating Load
For the building heating load, ventilation heat losses are treated differently from transmission losses:
Standard Method (Conservative)
Sum of all room ventilation losses = Building ventilation loss
Extended Method (More Realistic)
Takes into account:
- Simultaneity: Not all rooms are ventilated at the same time
- Heat transfer: Warm extract air from one room preheats others
- Infiltration balance: Pressure effects
Note: Our heating load calculator uses the standard method for safe system sizing. Actual ventilation losses may be lower in operation.
Common Mistakes to Avoid
1. Underestimating Ventilation Heat Losses
In well-insulated new buildings, ventilation losses can account for over 50% of the heating load!
2. Not Retrofitting After Window Replacement
New, airtight windows drastically reduce infiltration. Without controlled ventilation, problems arise:
- Moisture damage
- Mould growth
- Poor air quality
3. Overestimating HRV Efficiency
The manufacturer's efficiency rating applies only under laboratory conditions. Realistic deductions:
- Frost protection: -5 to -10%
- Leakage: -2 to -5%
- Lack of maintenance: -5 to -15%
Measures to Reduce Losses
1. Improve Building Airtightness
| Measure | Typical cost | n50 improvement |
|---|---|---|
| Seal windows | £40–80/window | -0.5 to -1.0 1/h |
| Insulate roller shutter boxes | £25–50/unit | -0.2 to -0.5 1/h |
| Seal penetrations | Variable | -0.5 to -1.0 1/h |
2. Retrofit Ventilation System with HRV
| System | Typical cost | HRV efficiency |
|---|---|---|
| Decentralised units (pair) | £650–1,200 | 70–85% |
| Central MVHR | £6,500–12,000 | 80–95% |
3. Optimise Ventilation Behaviour
- Purge ventilation rather than constant trickle
- Cross-ventilation for rapid air exchange
- Demand-controlled ventilation (CO2 sensor)
The Heating Load Calculator
Our heating load calculator considers all ventilation aspects:
- Room-by-room air change rates according to use
- Various ventilation concepts (natural, mechanical)
- Heat recovery with adjustable efficiency
- Infiltration calculation based on building airtightness
Calculate now: Determine the ventilation heat losses for your building with our heating load calculator.
Further Reading
- What is Heating Load? – The fundamentals of heating load calculation
- Transmission Heat Losses – Heat losses through the building envelope
- The U-Value Explained – The key building component metric
- Renovation Recommendations – Measures to reduce heating load
Sources
- DIN EN 12831-1:2017-09 – Method for calculation of the design heat load
- DIN 1946-6 – Ventilation of dwellings
- DIN EN 13829 – Blower door test