pv-calor.com
Radiator Optimisation: Efficient Heating with Correct Sizing Icon

Radiator Optimisation: Efficient Heating with Correct Sizing

The heat transition is in full swing: heat pumps are increasingly replacing oil and gas heating systems. But for a heat pump to work efficiently, the radiators must be correctly sized. In this article, you will learn why this is so important and how to optimise your radiators.

Why Is Radiator Sizing So Important?

The Problem: Old Radiators, New Heat Pump

Many existing buildings have radiators designed for high flow temperatures (65–75°C). Heat pumps, however, work most efficiently at low flow temperatures (35–55°C).

Flow Temperature Typical SPF (Air-Water HP) Electricity Consumption
35°C 4.5–5.0 Very low
45°C 3.5–4.0 Low
55°C 2.8–3.2 Medium
65°C 2.2–2.6 High

Rule of thumb: Each degree Celsius lower flow temperature improves the seasonal performance factor (SPF) by about 2.5%. Reducing from 55°C to 45°C saves around 25% electricity!

The Solution: Adapt Radiators

To heat with low flow temperatures, the radiators must deliver sufficient heat output. The options:

  1. Check existing radiators – Often they are already adequate
  2. Replace individual radiators – Only where necessary
  3. Upgrade radiator type – Same size, higher output
  4. Add heating surfaces – Supplement with underfloor heating

Basics of Radiator Output

Understanding Nominal Output

Every radiator has a nominal output (in watts), measured under standardised conditions:

Parameter Standard Value (EN 442)
Flow temperature 75°C
Return temperature 65°C
Room temperature 20°C
Excess temperature 50 K

The excess temperature (ΔT) is the difference between the mean heating water temperature and the room temperature:

ΔT = (Flow + Return) / 2 - Room temperature

Output at Other Temperatures

The actual heat output depends strongly on the excess temperature:

System Temperature Excess Temperature Output (relative)
75/65°C 50 K 100%
55/45°C 30 K ~49%
45/35°C 20 K ~28%
35/28°C 11.5 K ~13%

Important: A radiator with 1,000 W nominal output delivers only about 490 W at 55/45°C – less than half! This must be considered during planning.

The Radiator Exponent

The output reduction at lower temperatures is described by the radiator exponent (n):

Radiator Type Exponent n Characteristic
Column radiator 1.20–1.30 Strongly temperature-dependent
Panel radiator (Type 10) 1.25–1.30 Strongly temperature-dependent
Panel radiator (Type 21/22) 1.30–1.35 Moderately temperature-dependent
Convectors 1.35–1.45 Moderately temperature-dependent
Underfloor heating 1.00–1.10 Slightly temperature-dependent

The higher the exponent, the more the output drops at lower temperatures.

Comparing Radiator Types

Understanding the Type Designation

Panel radiators are classified by their construction:

Type Panels Convectors Output (relative)
Type 10 1 0 45%
Type 11 1 1 63%
Type 20 2 0 70%
Type 21 2 1 85%
Type 22 2 2 100%
Type 33 3 3 135%

Output Comparison at the Same Size

A radiator measuring 1600 × 500 mm delivers depending on type:

Type Nominal Output (75/65/20) At 55/45°C At 45/35°C
Type 11 ~800 W ~390 W ~225 W
Type 21 ~1,100 W ~540 W ~310 W
Type 22 ~1,350 W ~660 W ~380 W
Type 33 ~1,800 W ~880 W ~505 W

Optimisation strategy: By replacing a Type 11 radiator with a Type 33 at the same size, you can increase output by a factor of 2.25 – without changing the pipework!

Hydraulic Balancing

Why Is Balancing Important?

Hydraulic balancing ensures that each radiator receives exactly the right amount of water flow. Without balancing:

  • Nearby radiators become too hot
  • Distant radiators do not warm up enough
  • Flow temperature must be unnecessarily high
  • Energy waste of up to 15%

Types of Hydraulic Balancing

Method Description Accuracy
Method A Approximate by heating surface Low
Method B Based on heating load calculation High
Automatic Self-regulating valves Medium-High

Prerequisites

For correct hydraulic balancing, you need:

  1. Room-by-room heating load calculation according to DIN EN 12831
  2. Pre-settable thermostatic valves on all radiators
  3. Radiator characteristic curves (from the manufacturer)
  4. Pump sizing appropriate to the volume flow

When Must Radiators Be Replaced?

Indicators of Undersizing

Symptom Possible Cause
Room does not get warm enough Radiator too small
Very high flow temperature required Total heating surface too small
Radiator constantly running at maximum No output reserve
High electricity costs with heat pump Flow temperature too high

Calculating the Coverage Rate

The coverage rate shows whether a radiator is adequately sized:

Coverage rate = (Actual output / Required output) × 100%

Coverage Rate Rating Action
< 70% Critical Immediate replacement
70–90% Undersized Replacement recommended
90–100% Borderline Check
100–130% Optimal No change
> 130% Oversized Downsizing possible

Radiator Optimisation in the PV-Calor Heating Load Calculator

Our heating load calculator offers intelligent radiator optimisation that automatically identifies improvement potential:

Radiator optimisation in the heating load calculator The 2-stage analysis shows specific optimisation suggestions per room

The 2-Stage Analysis

Our algorithm checks two optimisation strategies:

Stage 1: Upgrade to maximum output

  • Retaining the current radiator dimensions
  • Switching to a higher-output type (e.g. Type 11 → Type 33)
  • Minimal installation effort

Stage 2: Downsizing where possible

  • With over-provision: Smaller radiator sufficient
  • Cost savings on new purchase
  • Aesthetic improvement (less bulky radiators)

System-Wide Effects

The analysis shows the effects on the overall system:

Parameter Meaning
Current flow temperature Temperature currently required
Possible new flow temperature Achievable after optimisation
Energy savings Percentage savings through lower flow temp
Annual heat demand current Before optimisation
Annual heat demand optimised After optimisation

Room-by-Room Results

For each room, you receive:

Information Description
Required output Required heat output per heating load calculation
CURRENT state Current radiator type and output
Coverage rate CURRENT Current over/under-provision
OPTIMISED Recommended radiator type
Coverage rate NEW After optimisation (always ≥100%)
Replacement costs Rough cost guidance

Fan Convectors as an Option

For particularly critical rooms with limited space, fan convectors can be activated:

Property Advantage Disadvantage
High output density Compact design Fan electricity consumption
Fast response Short warm-up time Noise
Low flow temp possible Ideal for heat pump Regular maintenance

Practical Optimisation Tips

Step-by-Step Procedure

  1. Carry out heating load calculation

    • Room-by-room calculation per DIN EN 12831
    • Record all rooms
  2. Survey existing radiators

    • Document type and dimensions
    • Determine nominal output (nameplate or manufacturer data)
  3. Calculate coverage rate

    • For desired flow temperature
    • Identify critical rooms
  4. Plan optimisation measures

    • Prioritise by coverage rate
    • Check cost-benefit ratio
  5. Carry out hydraulic balancing

    • After radiator replacement
    • Documentation for BAFA subsidy

Cost Guidance for Radiator Replacement

Radiator Size Material Installation Total
Small (up to 1000 W) €150–250 €100–150 €250–400
Medium (1000–1500 W) €250–400 €120–180 €370–580
Large (over 1500 W) €400–700 €150–220 €550–920

Subsidy Opportunities

Radiator replacement as part of a heat pump installation can be subsidised:

Subsidy Rate Requirement
BAFA heating optimisation 15–20% Hydraulic balancing
KfW 458 (with HP) Up to 70% New heat pump installation
Tax reduction 20% Owner-occupation, old building

Tip: Hydraulic balancing according to Method B (with heating load calculation) is a prerequisite for many subsidy programmes. Our heating load calculation provides all required data!

Special Cases and Alternatives

Retrofitting Underfloor Heating

In some rooms, retrofitting underfloor heating makes sense:

Situation Recommendation
Bathroom renovation planned Underfloor heating in bathroom ideal
Large living area Underfloor heating as base load
Low ceiling height Underfloor heating instead of large radiators
Allergy sufferers in household Underfloor heating minimises dust circulation

Infrared Heating as Supplement

For rarely used rooms, infrared heating can be sensible:

  • No water connection needed
  • Quick heat on demand
  • But: Higher operating costs

High-Temperature Heat Pump

Modern heat pumps can also deliver higher flow temperatures:

Heat Pump Type Max. Flow Temperature Efficiency
Standard 55°C Very good
Medium-temperature 65°C Good
High-temperature 70–75°C Satisfactory

Note: High-temperature heat pumps are more expensive and less efficient. Optimising the radiators is almost always more economical!

Conclusion

Key Point: Radiator optimisation is the key to efficient heat pump operation. By replacing undersized radiators with higher-output types, the flow temperature can often be reduced by 10–15 K – saving up to 30% electricity. Our heating load calculator automatically identifies critical rooms and suggests specific optimisations. Hydraulic balancing according to Method B completes the measure and is a prerequisite for many subsidy programmes.

Try it now: Go to the Heating Load Calculator with Radiator Optimisation

Further Reading

Sources

  • DIN EN 12831-1: Heating load calculation
  • DIN EN 442: Radiators – Heat output
  • VDI 6030: Designing room heating surfaces
  • VDI 4645: Planning and dimensioning of heat pump systems